Showing posts with label Pressure Measurement. Show all posts
Showing posts with label Pressure Measurement. Show all posts

Tuesday, March 27, 2012

Pirani gauge – A Thermal conductivity Gauge

The Pirani Gauge is a type of Thermal Conductivity Gauges.

Basic principle of Pirani gauge

A conducting wire gets heated when electric current flows through it. The rate at which heat is dissipated from this wire depends on the conductivity of the surrounding media. The conductivity of the surrounding media inturn depends on the densisty of the surrounding media (that is, lower pressure of the surrounding media, lower will be its density). If the density of the surrounding media is low, its conductivity also will be low causing the wire to become hotter for a given current flow, and vice versa.

Description of Pirani gauge

Pirani gaugeThe main parts of the arrangement are:
  1. A pirani gauge chamber which encloses a platinum filament.
  2. A compensating cell to minimize variation caused due to ambient temperature changes.
  3. The pirani gauge chamber and the compensating cell is housed on a wheat stone bridge circuit as shown in diagram.

Operation of Pirani gauge

  1. A constant current is passed through the filament in the pirani gauge chamber. Due to this current, the filament gets heated and assumes a resistance which is measured using the bridge.
  2. Now the pressure to be measured (applied pressure) is connected to the pirani gauge chamber. Due to the applied pressure the density of the surrounding of the pirani gauge filament changes. Due to this change in density of the surrounding of the filament its conductivity changes causing the temperature of the filament to change.
  3. When the temperature of the filament changes, the resistance of the filament also changes.
  4. Now the change in resistance of the filament is determined using the bridge.
  5. This change in resistance of the pirani gauge filament becomes a measure of the applied pressure when calibrated.

Note: [higher pressure – higher density – higher conductivity – reduced filament temperature – less resistance of filament] and vice versa.

Applications of Pirani gauge

Used to measure low vacuum and ultra high vacuum pressures.

Advantages of Pirani gauge

  1. They are rugged and inexpensive
  2. Give accurate results
  3. Good response to pressure changes.
  4. Relation between pressure and resistance is linear for the range of use.
  5. Readings can be taken from a distance.

Limitations of Pirani gauge

  1. Pirani gauge must be checked frequently.
  2. Pirani gauge must be calibrated from different gases.
  3. Electric power is a must for its operation.

Wednesday, December 15, 2010

Pressure Measuring Instruments


McLeod Vacuum Gauge

A known volume gas is compressed to a smaller volume whose final value provides an indication of the applied pressure. I have given a brief post on the equations used with good construction diagram of McLeod Vacuum Gauge

Strain Gauge Pressure Cell

Based on a principle

When a closed container is subjected to the appilied pressure, it is strained (that is, its dimension changes). Measurement of this strain with a secondary transducer like a strain gauge ( metallic conductor) becomes a measure of the appilied pressure.

The Two types of Strain Gauge Pressure Cell, Flattened tube pressure cell and Cylindrical type pressure cell are discussed.

Elastic diaphragm gauges

When an elastic transducer (diaphragm is this case) is subjected to a pressure, it deflects. This deflection is proportional to the appilied pressure when calibrated.

Bourdon tube Pressure Gauge

when an elastic transducer ( bourdon tube in this case ) is subjected to a pressure, it defects. This deflection is proportional to the applied pressure when calibrated.

Manometer with equal unequal limb types

This is the most simple and precise device used for the measurement od pressure. It consists of a transparent tube constructed in the form of an elongated 'U', and partially filled with the manometeric fliud such as mercury. The purpose of using mercury as the manometeric fluid is that their specific gravity at various temperatures are known exactly and they dont stick to the tube. The two common types of manometers are the equal limb type and unequal limb type.

Dead Weight Tester

The dead weight tester apparatus consists of a chamber which is filled with oil free impurities and a piston – cylinder combination is fitted above the chamber as shown in diagram. The top portion of the piston is attached with a platform to carry weights. A plunger with a handle has been provided to vary the pressure of oil in the chamber. The pressure gauge to be tested is fitted at an appropriate plate.

Pressure Measurement using U-tube Manometer
A well known very simple device used to measure the pressure is the U-tube manometer. The name U-tube is derived from its shape. U-tube manometer is shown below.

Terms related to pressure

All the important terms related to Pressure measurement like Atmospheric pressure, Absoulte pressure, Gauge Pressure, Vacuum pressure, Static Pressure, Total or Stagnation pressure, Dynamic – or – Impact – or – Velocity pressure and more are discussed.

And This Post will be updated regularly whenever i post a topic about pressure measurement using different devices.

Please Post your Comments below.

Thursday, December 2, 2010

McLeod Vacuum Gauge

Basic Principle of McLeod Vacuum Gauge:


A known volume gas is compressed to a smaller volume whose final value provides an indication of the applied pressure. The gas used must obey Boyle’s law given by;

P1V1=P2V2

Where, P1 = Pressure of gas at initial condition (applied pressure).
P2 = Pressure of gas at final condition.
V1 = Volume of gas at initial Condition.
V2 = Volume of gas at final Condition.

Initial Condition == Before Compression.
Final Condition == After Compression.

A known volume gas (with low pressure) is compressed to a smaller volume (with high pressure), and using the resulting volume and pressure, the initial pressure can be calculated. This is the principle behind the McLeod gauge operation.

Description of McLeod Vacuum Gauge:


The main parts of McLeod gauge are as follows:
McLeod vacuum gauge

A reference column with reference capillary tube. The reference capillary tube has a point called zero reference point. This reference column is connected to a bulb and measuring capillary and the place of connection of the bulb with reference column is called as cut off point. (It is called the cut off point, since if the mercury level is raised above this point, it will cut off the entry of the applied pressure to the bulb and measuring capillary. Below the reference column and the bulb, there is a mercury reservoir operated by a piston.

Operation of McLeod Vacuum gauge:


The McLeod gauge is operated as follows:

The pressure to be measured (P1) is applied to the top of the reference column of the McLeod Gauge as shown in diagram. The mercury level in the gauge is raised by operating the piston to fill the volume as shown by the dark shade in the diagram. When this is the case (condition – 1), the applied pressure fills the bulb and the capillary.
Now again the piston is operated so that the mercury level in the gauge increases.

When the mercury level reaches the cutoff point, a known volume of gas (V1) is trapped in the bulb and measuring capillary tube. The mercury level is further raised by operating the piston so the trapped gas in the bulb and measuring capillary tube are compressed. This is done until the mercury level reaches the “Zero reference Point” marked on the reference capillary (condition – 2). In this condition, the volume of the gas in the measuring capillary tube is read directly by a scale besides it. That is, the difference in height ‘H’ of the measuring capillary and the reference capillary becomes a measure of the volume (V2) and pressure (P2) of the trapped gas.

Now as V1,V2 and P2 are known, the applied pressure P1 can be calculated using Boyle’s Law given by;

P1V1 = P2V2

Let the volume of the bulb from the cutoff point upto the beginning of the measuring capillary tube = V

Let area of cross – section of the measuring capillary tube = a
Let height of measuring capillary tube = hc.

Therefore,

Initial Volume of gas entrapped in the bulb plus measuring capillary tube = V1 = V+ahc.

When the mercury has been forced upwards to reach the zero reference point in the reference capillary, the final volume of the gas = V2 +ah.

Where, h = height of the compressed gas in the measuring capillary tube
P1 = Applied pressure of the gas unknown.
P2 = Pressure of gas at final condition, that is, after compression
= P1+h

We have, P1V1 = P2V2 (Boyle’s Law)
Therefore, P1V1= (P1+h)ah

P1V1 = P1ah + ah^2

P1V1-P1ah = ah^2

P1 = ah^2/(V1-ah)

Since ah is very small when compared to V1, it can be neglected.

Therefore, P1 = ah^2/V1

Thus the applied pressure is calculated using the McLeod Gauge.

Applications

The McLeod Gauge is used to measure vacuum pressure.

Advantages of the McLeod Gauge:


  • It is independent of the gas composition.
  • It serves as a reference standard to calibrate other low pressure gauges.
  • A linear relationship exists between the applied pressure and h
  • There is no need to apply corrections to the McLeod Gauge readings.

Limitations of McLeod Gauge:


  • The gas whose pressure is to be measured should obey the Boyle’s law
  • Moisture traps must be provided to avoid any considerable vapor into the gauge.
  • It measure only on a sampling basis.
  • It cannot give a continuous output.

Wednesday, October 20, 2010

Strain Gauge Pressure Cell:

Basic Principle:


When a closed container is subjected to the appilied pressure, it is strained (that is, its dimension changes). Measurement of this strain with a secondary transducer like a strain gauge ( metallic conductor) becomes a measure of the appilied pressure.

That is, if strain gauges are attached to the container subjected to the applied pressure, the strain guages also will change in dimension depending on the expansion or contraction of the container. The change in dimension of the strain guage will make its resistance to change. This change in resistance of the strain gauge becomes a measure of pressure appilied to the container (elastic container or cell).

There are two types of strain gauge pressure cells namely:

  1. flattened tube pressure cell.
  2. Cylindrical type pressure cell.

Flattened tube pressure cell.


The main parts of the arrangement are as follows:

An elastic tube which is flat and pinched at its two end as shown in diagram.
Two strain gauges are placed on this elastic tube: one is on the top and other is at the bottom of this elastic tube.
One end of the elastic tube is open to receive the appilied pressure and its other end is closed.

Operation:


The pressure to be measured is appilied to the open of the tube. Due to pressure, the tube tends to round off, that is, the dimension changes (strained). As the strain gauge are mounted on the tube, the dimension of the strain gauges also change proportional to the change in dimension of the tube, causing a resistance change of the strain gauges. The change in dimension of the tube is proportional to the applied pressure. Hence the measurement of the resistance change of the strain gauges becomes a measure of the appilied pressure when calibrated.

Cylindrical Type pressure cells:


Description


The main parts of this arrangement ar as follows:

A cylindrical tube with hexagonal step at its centre. This hexagonal step helps fixing this device on to place where the pressure is to be measured.

The bottom portion of this cylindrical tube is thearded at its external and is open to receive the pressure to be measured.

The top portion of this cylindrical tube is closed and has a cap screwed to it.

On the periphery of the top portion of the cylindrical tube are placed two sensing resistance strain gauges.

On the cap (unstrained location) are placed two temperature compensating strain gauges.

Operation.

The pressure to be measured is appiled to the open end of the cylindrical tube. Due to the pressure, the cylindrical tube is strained, that is its dimension changes. As the strain gauges are mounted on the cylindrical tube, the dimension of the sensing strain gauges also change proportional to the change in dimension of the cylindrical tube, causing a resistance changes of the strain gauges.

The change in dimension of the cylindrical tube is proportional to appilied pressure.

Hence the measurement of the resistance change of the sensing strain gauges becomes a measure of the appilied pressure when calibrated.

Appilications of the strain gauge pressure cells


the flattened tube pressure cell is used for low pressure measurement.
The cylindrical type pressure cell is used for medium and high pressure measurement.

Monday, October 11, 2010

Elastic diaphragm gauges

Basic principle of Elastic diaphragm gauges:


when an elastic transducer (diaphragm is this case) is subjected to a pressure, it deflects. This deflection is proportional to the applied pressure when calibrated.

Description of Elastic diaphragm gauges:


The main parts of the diaphragm which is a thin circular plate (made of springy metal) is fixed firmly around its edges. The diaphragm may either be flat or corrugated.

Sunday, October 10, 2010

Bourdon tube Pressure Gauge


Basic Principle of Bourdon tube pressure gauge:


when an elastic transducer ( bourdon tube in this case ) is subjected to a pressure, it defects. This deflection is proportional to the applied pressure when calibrated.

Description of Bourdon tube Pressure Gauge:


The main parts of this instruments are as follows:

An elastic transducer, that is bourdon tube which is fixed and open at one end to receive the pressure which is to be measured. The other end of the bourdon tube is free and closed.

Friday, October 8, 2010

U-tube Manometer with equal unequal limb types

Description of manometer:


This is the most simple and precise device used for the measurement od pressure. It consists of a transparent tube constructed in the form of an elongated 'U', and partially filled with the manometeric fliud such as mercury. The purpose of using mercury as the manometeric fluid is that their specific gravity at various temperatures are known exactly and they dont stick to the tube. The two common types of manometers are the equal limb type and unequal limb type.

Operation of Manometer :


to measure the pressure of a fluid which is less dense and immisible with the manometeric fluid, it is appilied to the top of one of the limbs of the manometer while a reference fluid pressure (generally atmospheric ) is appilied to the other limb.

Let : P1 = unknown pressure with specific weight w1.
And : P2 = reference pressure with specific weight w2.
And : wm = specfic weight of the manometeric fluid.

The difference between the pressure on the two limbs of the manometer is a function of 'h', the difference between the levels of the manometeric fluid in the two limbs. 'h', can be read directly by placing a scale near the manometer.

For Equal Limb type:

equal limb type manometer



the pressure balance equation is

P1 + gh * w1 = P2 + gh * wm

therefore, differential pressure

P = P1 – p2 = gh(wm – w1)

 

For unequal Limb type


unequal limb type manometer
the pressure balance equation is : (section-XX)

P1+w1(h1+h2+h) = P2 + w2h2 + wmh

Therefore, differential pressure:

P = P1 – P2 = w2h2 + wm * h – w1(h1 + h2 + h)

= wm*h [ 1 + (w2/wm * h2/h) – w1/wm ( h1+h2/h + 1) ]

= wmh * Cn

where; Cn = [ 1 + ( w2/wm – h2/h) – w1/wm ( h1+h2/h + 1)]

Cn is known as hydraulic correction factor.

Applications of Manometer :


  • they are used to sense differential pressure in venturimeter and other flow meters.
  • They are used as level devices to sense liquid heads.
  • There are used as primary standard for pressure measurements.

Advantages of Manometer :


  • they are simple is construction.
  • They give accurate results.
  • Wide range of manometeric fluids ar available such as mercury, water, aniline, tetrabromethane, bromoform and carbon tetrachloride.

Disadvantages of Manometer :


  • They might break during transport.
  • Certain manometeric fluids cause hazards when exposed to atmosphere.
  • Error is introduced if the diameter of the tube is less.
  • Leveling is required.

Thursday, October 7, 2010

Dead Weight Tester

Description


The dead weight tester apparatus consists of a chamber which is filled with oil free impurities and a piston – cylinder combination is fitted above the chamber as shown in diagram. The top portion of the piston is attached with a platform to carry weights. A plunger with a handle has been provided to vary the pressure of oil in the chamber. The pressure gauge to be tested is fitted at an appropriate plate.

Operation


the dead weight tester is basically a pressure producing and pressure measuring device. It is used to calibrate pressure gauges. The following procedure is adopted for calibrating pressure gauges. Calibration of pressure gauge means introducing an accurately known sample of pressure to the gauge under test and then observing the response of the gauge. In order to create this accurately known pressure, the following steps are followed.

The valve of the apparatus is closed.
A known weight is placed on the platform.
Now by operating the plunger, fluid pressure is applied to the other side of the piston until enough force is developed to lift the piston-weight combination. When this happens, the piston weight combination floats freely within the cylinder between limit stops.

In this condition of equilibrium, the pressure force of fluid is balanced against the gravitational force of the weights puls the friction drag.

Therefore, PA = Mg + F

Hence : P = Mg + F / A

where, P = pressure
M = Mass; Kg
g = Acceleratoion due to gravity ; m/s²
F = Friction drag; N
A = Eqivalent area of piston – cylinder combination; m²

Thus the pressure P which is caused due to the weights placed on the platform is calculated.

After calculating P , the plunger is released.

Now the pressure gauge to be calibrated is fitted at an appropriate place on the dead weight tester. The same known weight which was used to calucated P is placed on the platform. Due to the weight, the piston moves downwards and exerts a pressure P on the fluid. Now the valve in the apparatus is opened so that the fluid pressure P is transmitted to the gauge, which makes the gauge indicate a pressure value. This pressure value shown by the gauge should be equal to the known input pressure P. If the gauge indicates some other value other than p the gauge is adjusted so that it reads a value equal to p. Thus the gauge is calibrated.

Applications:


It is used to calibrated all kinds of pressure gauges such as industrial pressure gauges, engine indicators and piezoelectric transducers.

Advantages:


it is simple in construction and easy to use.
It can be used to calibrated a wide range of pressure measuring devices.
Fluid pressure can be easily varied by adding weights or by changing the piston cylinder combination.

Limitations:


the accuracy of the dead weight tester is affected due to the friction between the piston and cylinder, and due to the uncertainty of the value of gravitational constant 'g'.

Tuesday, October 5, 2010

Pressure Measurement Devices

Gravitational transducers

  1. A dead weight tester
  2. Manometer

Elastic transducers ( Force summing Transducers)

  1. Bourdon tube pressure gauge
  2. elastic diaphragm gauges
  3. bellow gagues
  4. Bellow gaugues to measure gauge pressure
  5. Bellow gauge to measure differential pressure

Strain gauge pressure cells.

  1. Flattened tube pressure cell (PINCHED TUBE).
  2. Cylindrical type pressure cell.

Mcleod vacuum gague.

  1. Thermal conductivity gauges.

Pirani gauge.
  1. Thermocouple typre conductity gauge.

Ionisation gauge
  1. bulk modulus or electrical resistance pressure gauge.

The above instruments are used in following situations:


Type of pressure to be measured
Pressure Measuring instrument to be used
Low pressure
Manometer
High and medium pressure
Bourdon tube pressure gauge.
Diaphragm gauge.
Bellows Gauges.
Low vacuum and ultra high vacuum
Mcleod vacuum gauge
thermal conductivity gauges.
Ionisation gauges.
Very high presures
Bourdon tube pressure gauge.
Diphragm gauge.
Bulk modulus pressure gauge.

Monday, October 4, 2010

Terms related to pressure

Atmospheric pressure:


The pressure due to air surrounding the earths surface is called as atmosperic pressure.

Absoulte pressure:

It is known that pressure is force per unit area when the interaction of fluid particles among themselves is zero, a zero pressure intensity will occur. This is possible only when the population of molecules is negligibly small which is nothing but perfect vacuum. Hence the pressure intensity measured from a state of prefect vacuum is called as absoulte pressure.

Gauge Pressure:


A pressure measuring instrument generally measures the difference between the uknown pressure (p) and the atmospheric pressure (pa). When the unknown pressure (P) is greater than the atmospheric pressure (Pa), the pressure measured by the instrument is called as the gauge pressure.

Vacuum pressure:


A Pressure measuring instrument generally measures the difference between the unknown pressure (P) and the atmospheric pressure (Pa). When the atmospheric pressure (Pa) is greater than the unknown pressure(P), the pressure mesured by the instrument is called as the vacuum pressure.

Static Pressure:


the pressure caused on the walls of the pipe due to a fluid at rest inside the pipe or due to the flow of a fluid parallel to the walls of the pipe is called as static pressure. This static pressure is measured by inserting a pressure measuring tube into the pipe carrying the fluid, so that the tube is at right angle to the fluid flow path.
Pressure relation


Total or Stagnation pressure:


the pressure which is obtained by bringing the flowing fluid to rest isentropically is called as total or stagnation pressure. Hence the pressure will be a sum of static pressure and impact pressure.

Dynamic – or – Impact – or – Velocity pressure.


The pressure due to fluid velocity (flow speed) is called as impact pressure.

Impact pressure = Total pressure – static pressure.

Sunday, October 3, 2010

Introduction to pressure measurement

It is time to know about pressure measurement..

    In general, pressure is represented as force per unit area. The measurement of pressure is one of the most important measurements, as it is used in almost all industries. Some important appilications of pressure measurement is listed.

Thursday, May 27, 2010

Pressure Measurement using U-tube Manometer

         A well known very simple device used to measure the pressure is the U-tube manometer. The name U-tube is derived from its shape. U-tube manometer is shown below,


Construction of U-tube Manometer:


Let me explain you about the construction about the u-manometer. This manometer consists of a U shaped tube in which the manometeric liquid is filled. The manometer is used to measure the pressure which is unknown by the balancing gravity force and acceleration due to gravity, g = 9.81 m/sec2

u-tube-manometer
The manometer consists of a steel, brass and aluminum material. It has a glass tube made up of pyralex glass. The graduations are made on the tube in terms of mm or in some condition it is graduated in kilo Pascal.

Working of U-tube Manometer:

The unknown pressure is applied in the one arm of the tube and the mercury in the tube or manometeric liquid filled in the tube moves in the tube or rises to the constant region and then the movement is stopped. The height of the liquid is measured and noted. The pressure is calculated by using the formula,

                                                                    P1-P2 = Pmhg

The above equation is arrived by

P1 = Pthg = P2+Pmhg
P1-P2 = hg(Pt – Pm)

P1 = applied pressure
P2 = 0
Pt = specific gravity of the liquid or water
g = acceleration due to gravity.
P1 – P2 is approximately equal to Pmhg.


Advantages of U-tube Manometer:

  1. Simple in construction
  2. Low cost
  3. Very accurate and sensitive
  4. It can be used to measure other process variables.

Disadvantages of U-tube Manometer:

  1. Fragile in construction.
  2. Very sensitive to temperature changes.
  3. Error can happen while measuring the h.

Characteristics of liquid used in U-tube Manometer:

  1. Viscosity should be low.
  2. Low surface tension is required.
  3. The liquid should stick on the walls.
  4. Should not get vaporized.